In this paper, design study and evaluation related with safety design criteria (SDC) and safety design guideline (SDG) on the balance of plant (BOP) of the demonstration JSFR including fuel handling system, power supply system, component cooling water system, building arrangement are reported. For the fuel handling system, enhancement of storage cooling system has been investigated adding diversified cooling systems. For the power supply, existing emergency power supply system has been reinforced and alternative emergency power supply system is added. For the component cooling system, requirements and relation with safety grade components are investigated. Additionally for the component cooling system, design impact when adding decay heat removal system by sea water has been investigated. For reactor building, over view of evaluation on the external events and design policy for distributed arrangement is reported. Those design study and evaluation provides background information of SDC and SDG.