Stupa of State Preceptor Jigwang at Beopcheonsa temple site, Wonju, was conserved and restored in 1957. It was necessary to assess the degree of damage to the used mortar and to provide objective data on the necessity of its removal. Therefore, the HCP(half-cell potential) measurement used in concrete fields was applied. Multi-regression analysis of HCP data, following the rapid corrosion test of the roofstone mortar used by the rebar, resulted in a high correlation of HCP values(0.86), depending on the amount of corrosion and cover depth used for the steel bar. As a result, high correlation values(0.86) for the coefficients of determination were derived. The showed that the measurement of the wet conditions -431 to -663 mV on the roofstone indicated a corrosion damage rate of 90% or more after removal and restoration.